Calculated fill—
Maximum allowed—
Used conductor area—
Allowable fill area—
Total conductors—
Remaining allowable area—
Status: Add conductors to calculate.
A minimum conduit-size recommendation will appear here.
| Conductor | Qty. | Area each | Total area |
|---|
| No calculation yet. |
This tool uses 53% for one cable or conductor, 31% for two, and 40% for three or more. Cat5e, Cat6, coaxial, and security-cable values are based on representative outside diameters and can vary materially by manufacturer, shielding, listing, and jacket construction. Use the Custom Cable OD option for manufacturer-specific dimensions. Verify the adopted NEC edition, cable listing, raceway dimensions, cable-bending limits, pulling requirements, derating, firestopping, separation rules, and local authority requirements before construction.